- DVOP-iOC-DH42Intelligent monitoring box
DVOP-iOC-DH42 intelligent monitoring box comes with intelligent monitoring operation and maintenance system data acquisition and remote control function, can identify the fault type through the front-end data return, and can remotely restart the camera and other external equipment, eliminating part of the field maintenance work. At the same time, the intelligent ordering function of accurate fault location can send orders on demand, saving labor costs. For the manual inspection work of traditional operation and maintenance, the blindness and complexity of manual inspection are fundamentally solved due to the real-time monitoring function and background analysis and display function of the software. The monitoring operation and maintenance management platform provides remote monitoring, data analysis and statistics, equipment ledger, intelligent order sending and other functions, and has a remote restart function, which can remotely restart the chassis, cameras, strobe lights, and other access devices. Achieve intelligent operation and maintenance management to ensure the online rate of the camera.
According to the specific situation of the project area, the internal functional modules of the box are customized to meet the needs of different application environments and customers. Smart box products are widely used in safe city, Xueliang engineering, intelligent transportation, building monitoring, forest fire monitoring, electricity, water conservancy and other industry monitoring fields.
● 2P25A air switch 1 + ground copper bar;
item |
Stats |
Specification parameters |
Box routine |
Material |
Box spray plastic using high quality cold rolled plate, plate thickness 1.5mm;Galvanized steel plate is optional |
Grade of protection Environmental monitoring content |
IP55 Temperature and humidity, current, voltage |
|
Standard Accessories |
Fan, LED light, mechanical door status detection switch, optical fiber fusion disk, optical fiber Couplers |
|
Accessories of choice |
Password keyboard, heating resistor, strobe light, water leak detection unit |
|
Installation method |
Ground, hanging pole optional |
|
Automatic reclosing |
Operating voltage Un |
85~300 VAC |
Rated load current |
6A-63A Optional/adjustable |
|
Overcurrent as current |
1.151 n |
|
Leakage no action current |
|
|
Leakage action current |
15 mA |
|
Overvoltage action voltage |
280V±5V(adjustable) |
|
Undervoltage operating voltage |
150V±5V(adjustable) |
|
Overcurrent disconnect action time |
3 + / - 0.5 s |
|
Short circuit disconnect action time |
0.1 or lesss |
|
Leakage disconnect action time |
< 0.1 s |
|
Over pressure, under pressure
Disconnect action time
|
< 0.5 s |
|
Allow reset load impedance |
10 2 |
|
Voltage detection before closing |
There are |
|
Reclosing time |
60s/120s/180s/300s+N times adjustable |
|
Dc 12V power supply monitoring
And Control
|
Monitoring port |
Each DC12V monitoring module supports up to 8 remote monitoring current, voltage and control power supplies Off. |
Rated load current |
2A per way |
|
Data acquisition and remote
Control
|
Data interface |
2 RS485, 4 DI, 6 D0, 1 10M/100M network port |
Lightning strike monitoring port |
1 way |
|
Water Leak detection port |
1 way |
|
Heating resistance control port |
1 way |
|
Temperature and humidity measurement range |
Temperature :-40℃~125℃ |
|
|
Humidity :0~100%rh |
|
Temperature and humidity measurement accuracy |
Temperature :±0.3℃ umidity :±2%rh |
|
Strobe light brightness adjustment |
1 way DC12V 0-1A |
|
Sensor as standard |
Temperature and humidity sensor, light sensor |
|
Optical fiber communication |
Access method |
10/100/1000Mbps |
Protocol Standards |
IEEE802.310Base-T Ethernet,IEEE802.3u, 100Base-TX/FX Fast Ethernet |
|
Wavelength |
850nm/1310nm/1550nm |
|
Transmission distance |
Five types of twisted pair :100m Double fiber multi-mode :2Km Dual fiber single mode :25/40/60/80/100/120Km Single fiber single mode :25/40/60/80/100Km |
|
Ports |
4-8 RJ45 ports: Connect STP/UTP Category 5 twisted pair cables, including 1 RJ45 maintenance port (Optional) |
|
1/2 fiber port: dual fiber multi-mode SC/ST/FC(fiber size 50, 62.5/125hm); Dual-fiber single-mode SC/ST/FC(fiber size 9/125Hm); Single fiber single mode SC/FC(fiber ruler Inch 9/125μm) |
||
Conversion method |
Medium conversion, store and forward/through |
|
MAC Address Table |
8K |
|
Cache |
1 Mbit |
|
Flow control |
Full duplex state: flow control, half duplex state: back pressure mode |
|
Ring network protocol |
|
|
Delay |
Support STP/RSTP spanning tree, support
ERPS industrial ring network, self-healing time ≤50ms
Store and forward :9.6us, through :0.9us
|
|
Bit error rate |
The < 1/1000000000 |
|
Power supply Lightning protection
Performance
|
Maximum sustainable operating voltage |
Uc:385V AC |
Nominal discharge current |
In:20kA(8/20us) |
|
Maximum discharge current |
Imax:40kA(8/20us) |
|
Voltage protection level |
Up:1700V(In under) |
|
Response time |
Ta:25ns |
|
Reference standard |
GB18802.1 2010 YD1235 IEC61643 |
|
Network Lightning protection
Performance
|
Maximum sustainable operating voltage |
Uc:6V |
Composite wave test |
C2:5 kv / 2.5 kA |
|
Voltage protection level |
Up: line-ground 600V Line-to-line 25V |
|
Transfer rate |
Vs:100Mbps |
|
Reference standard |
GB18802.21 2010 IEC61643 |
|
Electrostatic discharge immunity |
Contact discharge reactance |
4KV |
Air discharge reactance |
8KV |